仅用于营销枢纽云系统实施过程中的预览与测试,正式运营之前,请绑定私有独立域名。 注册域名

仅用于营销枢纽云系统实施过程中的预览与测试,正式运营之前,请绑定私有独立域名。 注册域名

186-9497-0015

Micom P24x Lockdown Protection function

publish:2025-01-03 10:00:00   views :959
publish:2025-01-03 10:00:00  
959



P24x's jam-spin protection consists of three functions: startup timeout detection, jam-spin detection during startup; Jam spin detection. The three-part functionality can be enabled or turned off separately. 

The criteria for motor starting conditions are optional: 52a, starting current or 52a + l.

The locked rotation detection during the motor starting process is used when the starting time is greater than the safe locked rotation time. At this time, it needs to cooperate with the optical input switch of the speed detection switch 

Rationing Speed Input(DDB 104)。 In addition, the internal logic of this function is also related to the closing signal of the circuit breaker, and 52a needs to be allocated. The action logic of this component is: when the current exceeds the block current and the speed switch input 0, the protection will act after the block protection delay time. 

 

  Tel

  18694970015

  Email

  sales@njzndq.com 

     WeChat 

   

WeChat QR code
Nanjing Zhuneng Electric Co., Ltd

Mobile number: 18694970015

WeChat: power1411913

Email: sales@njzndq.com

Address: Building 16, Liandong U Valley Industrial Park, No.24 XuefuRoad, Jiangbei New District, Nanjing, Jiangsu, China

Copyright © 2024 Guodian Nanjing Automation Co., Ltd. All rights reserved.
Contact
Navigation
WhatsApp
Powered by Feedback Manage